MZAOV 3A Single Zone – Non Extendable

Product code: MZAOV-1001A

MZAOV control panel with 3 amp integral power supply. Single detection zone, non extendable. Large graphical LCD display. This purpose designed single detection zone automatic opening vent control panel has been developed to provide a comprehensive and flexible solution to smoke vent control scenarios and is suitable for use with vents, windows and roof lights.

Single ZoneTwin Wire

Where to buy
SKU: MZAOV-1001A Category: Brand: MZAOV

Product Features

  • 3 amp integral PSU
  • Large graphical display
  • Easy to program
  • Single detection zone, Conventional or Twin-wire.
  • Input from other detection systems, to activate
  • Monitored Actuator output for controlling smoke vents
  • Switch input to control wide combination of vents
  • Fireman switch input to override all other inputs
  • All inputs and actuator outputs monitored for Short and Open Circuit
  • User switch inputs configurable as local fireman switches
  • Thermostat input - Ventilation mode. Vents openable in 10% steps
  • Monitoring of unused inputs and outputs can be disabled

Technical Specifications

Enclosure1.2mm Mild Steel IP30. Colour ref: MW334E Interpon powder coat
Cable EntryVia 20mm knockouts located in the top and rear of the cabinet
DimensionsBack box: 375mm W x 345mm H x 110mm D Lid: 382mm W x 354mm H x 25mm D
Mains Supply3A internal switch mode power supply, Nom 27v DC
Battery Capacity2 x 12Ah 12v VRLA
Detection ZonesSingle monitored detection zone. EOL = 6K8
Twin WireSelectable in panel (enables AV devices to be connected to det cct)
On Board Relays1 x Alarm, 1 x Fault, volt free changeover, Max 3A
Fireman’s Switch InputFireman’s control switch input for Open/Close/Auto
Vent Control InputVent control switch input, Open/Close (rocker switch)
Actuator OutputReversal actuator control output (2.5A total max) can be configured as a maintained output for a magnetic door
Inrush Current20A for an interval of 2 seconds
Aux Output1 voltage free normally open relay contact, closing when the associated zone is activated, Max 3A
False Alarm ManagementType A, B and C dependency mode, approved by LPCB