Product Features
- 10A EN54 Approved Power Supply
- Dual Supply Outputs as standard
- Failsafe fault relay output
- 2 x 38Ah Batteries
- Robust Metal Enclosure
- Healthy Supply (Green) and Fault Condition (Yellow) LED indicators
The Haes 10A EN54 Power Supply Unit has been developed to provide a simple to use, robust solution for fire alarm applications where mandatory EN54 part 4 approval is required.
This includes applications where detection devices are not powered directly from the fire alarm control equipment, for example; Beam Detectors, Aspirating Detectors and Flame Detectors. Other applications would be powering Sounder Circuit Controllers and Expanders, Control Panel Repeaters, Remote Communicators, or any other Fire Alarm System critical power supply applications.
As standard, the PSUs come with dual supply outputs, a failsafe fault relay output, and Supply Healthy and Fault Condition LED indicators.
Enclosure | Steel IP30. Epoxy powder coated Interpon Radon, silver grey. |
---|---|
Cable Entry | Fire resistant screened cable, minimum size 1 mm2. Max cable length 1 Km (20 Ohm). FireBurn, FP200 or equivalent (max capacitance 1uF, max inductance 1mH). |
Temperature Range | -5°C to +40°C Maximum relative humidity: 95% |
Dimensions (WxHxD) | 469 x 394 x 185 |
Terminal Capacity | 0.5mm2 to 2.5mm2 solid or stranded wire. |
PSU Input +/- to PCB | 29VDC supply input. Diode protected for reversal and independent short circuit. Max current 3 amps. Max input current 3 amps. Input voltage 29.0VDC to 30VDC. |
Temp Sense Input | Input for connection of battery temperature sensor. Attach to central point of sealed lead acid battery pair. Thermistor TTC5103 10,000 Ohms at 25°C. |
Battery Charger Output | 27.3VDC nominal at 20°C Temperature compensated |
Mains supply | 47-63Hz 2.5A @ 230VAC |
Mains supply fuse | 10A (T4A 250V) 320W unit. Not accessible for servicing. Internal to switch mode power unit |
Internal power supply rating | 10A total including battery charging. Maximum load shared between outputs: 7.5A |
Power supply output voltage | 19-29VDC |
Maximum ripple voltage | 200 mV p-p. Supply and charger fault monitored. |
Min current supplied by PSU (Imin) | 0A |
Country Of Origin | U.K. |
Battery charging voltage | 27.3VDC nominal at 20°C. Temperature compensated |
Battery charging current limit | 1.2A or 2.0A |
Max current drawn from batteries | 7.5A with main power source disconnected. Battery fuse 10A (5x20 glass, quick blow) |
Battery high impedance fault (Batt Hi Z) | Resistance > 1 Ohm 1-hour reporting time |
Battery type | YUASA NP38-12I (12V 38Ah) Fire Retardant |
Battery fuse | 10A |