Esprit-G Dual Flood Area 3.4A

Product code: ESG-1003

Dual flood area Automatic Extinguishant Release control panel with integral 3.4A power supply. Esprit-G control panels are fully configurable for extinguishant release scenarios including flexible zone voting for the gas release and programmable countdown timers to suit the exact requirements of the site. A large graphical display accommodates an easy-to-navigate menu system


Where to buy
SKU: ESG-1003 Category: Brand: Esprit

Product Features

  • Dual flooding areas
  • 6 detection zones
  • Approved to EN12094-1, EN54- 2, EN54-4
  • Fully configurable zone voting for gas release
  • 6 programmable sounder circuits
  • Configurable sounder delays
  • Zero time delay option for manual call points
  • Compatible with IS barriers
  • Non-latching zone input option
  • Extinguishant delay 0-60 seconds
  • Extinguishant duration 1-300 seconds
  • Flooding time 60-1800 seconds
  • Extract time 1-900 seconds
  • Graphical back lit LCD display
  • Access controls via key switch or code entry
  • Time and date stamped event log
  • Alarm counter
  • Company logo can be programmed in display
  • RS 485 communications for remote status units
  • Optional key switch status control
  • Fire, fault & stage signal relays
  • 2 amp actuator circuit
  • Hold, abort, flow switch, manual release, mode control and pressure switch monitoring inputs
  • 3.4 amp PSU for 18Ah batteries
Image of Esprit Extinguishant Release Control Panel

Technical Specifications

Enclosure1.2mm Mild Steel IP30. Colour ref MW334E Interpon Powder coat
Cable EntryVia 20mm knockouts located in the top and rear of the cabinet
DimensionsBack box: 450 W x 385 H x 100 D (mm), Lid: 463 W x 394 H x 25 D (mm)
Mains SupplyUniversal switch mode PSU, 3.4A
Battery CapacityUp to 18Ah 24V
Charger Current700mA
Auxiliary Supply400mA aux supply output (21-28vdc)
Detection Zones6 x conventional zones
Extinguishing Zones2 x flooding/extinguishing zones support for metron & solenoid type actuators
Sounder Circuits6 x 400mA 21-28vdc
On Board Relays10 x 1A 30VDC relay outputs, (fire, fault, stage 1 & 2, extract, local) x2
Programmable OutputsAdditional outputs via add on output card, ESG-2005. (1 card per flood zone)
Switch InputsCC, PULS
Monitored InputsFlow, Pressure, Release, Hold, Abort x 2
Countdown TimersExtinguishant Delay: 0-60 secs, Extinguishant Duration: 1-300 secs, Flooding Time: 60-1800 secs, Extract Time: 1-90 mins, Reset Inhibit Time: 0-30 mins
Event Log255 events, time & date stamped
Earth Fault MonitoringYes
Intrinsically Safe ModeSelectable for detection zones
Remote Status UnitsGraphic display & Mini version via RS485 up to 16 assignable to area
Display240 x 64 Graphical LCD backlit
Manual Release ButtonOnboard under plastic release cover x 2

Technical Specification

Product Downloads

The following downloads are available for this product:
Image of Esento LogoImage of AlarmSense LogoImage of AOV LogoImage of Esento Marine LogoImage of AlarmSense PLUS LogoImage of Esprit Logo