Esento Excel 12 Zone Conventional or Twin Wire

Product code: XLEN-12

12 zone Esento Excel fire alarm control panel. Excel panels provide the ultimate in flexibility, simplicity & reliability with a generous selection of programmable features, inputs and outputs. Fully networkable up to 8 control panels, 3 false alarm management modes, Twin Wire mode per zone and fully functional repeater panels.

Up to 12 zonesTwin WireNetworkingRepeatersLPCB-810a

Where to buy
SKU: XLEN-12 Category: Tags: , Brand: Esento

Product Features

  • 12 zones
  • Zonal Twin Wire selection by DIL switch
  • Network up to 8 control panels
  • Activate controls via key switch or code entry
  • Integral detector removal monitoring
  • 3 Amp switch mode power supply Nom 27V DC
  • 4 monitored sounder outputs
  • 2 Aux C/O relays (1 x Fire) (1 x Fault). voltage free
  • Class change I/P
  • Alert I/P
  • Fire & fault switched -ve outputs
  • Program delays to outputs
  • False alarm modes A, B & C
  • Test mode, with or without sounders
  • Disable zones, sounder O/Ps, aux O/Ps & delays
  • Alarm load, 2.4A shared between all sounder outputs
  • All sounder circuits are fused @ 500mA with resettable fuses
LPCB-810a

Technical Specifications

Enclosure1.2mm Mild Steel IP30. Colour ref: MW334E Interpon powder coat
Cable EntryVia 20mm knockouts located in the top and rear of the cabinet
DimensionsBack box: 450mm W x 300mm H x 85mm D, Lid: 460mm W x 310mm H x 25mm D
Mains Supply3A internal switch mode power supply, Nom 27v DC
Battery Capacity2 x 7.0Ah 12v VRSLA
Detection Zones12 x conventional or Twin Wire. EOL = 4K7R
Sounder Circuits4 x monitored, fused @500mA. EOL = 4K7R
Twin WireSelectable per zone
NetworkingUp to 8 control panels, fault tolerant RS485 communication, requires TPCA05 network card
On Board Relays2 x programmable, 3A, 30v volt free changeover, additional relay provided on high spec zone card
Outputs2 x programmable, 40mA switch -ve, 2 additional outputs provided on high spec zone card
Switch InputsClass change & alert (pulsing)
Event Log40 event history
Intrinsically Safe ModeSelectable per zone
False Alarm ManagementType A, B & C dependency modes, approved by LPCB
Delay TimerOn board programmable delay timer 1-10 mins

Technical Specification

Product Downloads

The following downloads are available for this product:
Image of Esento LogoImage of AlarmSense LogoImage of AOV LogoImage of Esento Marine LogoImage of AlarmSense PLUS LogoImage of Esprit Logo